5 / 5 page
Specifications are subject to change without notice (16.10.06)
5
Dimensions
22.5
99.5
28.5
DIN-rail
Note
When DPB01 or PPB01 is used with phase indicator lamps (see examples in the following diagrams), the lamp H1 or H2
might be dimly lit when there is a phase loss in L1 or L2. This might happen if the lamps used are the typical low power indi-
cator lamps, and there are no other loads present.
This fact can be avoided by using W4 models. Note that the neutral must be always connected to the device.
L2 L3
L1
L1
L2
L3
L1
L2
m<3
m
15
16
18
N
N
U
H1H2
H3
DPB01
L1
L2
L3
N
6 7
5
L1
L2
m<3
1
4
3
U
11
m
H1H2
H3
PPB01
36
94
28.5
90
Plug-in
DPB01, PPB01